120VAC 48VDC 2000VA 1600W Extreme Temperature Network UPS for Industrial and Traffic Networks, 3U, Hardwire
Product Name |
Eaton Tripp Lite series SmartPro extreme temperature UPS
|
Catalog Number |
SMART1548ET
|
UPC |
037332241207
|
Product Length/Depth |
9.45 in
|
Product Height |
5.24 in
|
Product Width |
15.75 in
|
Product Weight |
32.41 lb
|
Compliances |
RoHS
TAA Compliant |
Certifications |
UL 1778
CSA certified NOM |
Global Catalog |
SMART1548ET
|
Topology |
Line-interactive
|
Form factor |
Rackmount
|
Rack size |
3U
|
Package contents |
|
Input nominal voltage |
120 VAC
|
Nominal frequency |
50/60 Hz
|
Input frequency range |
50/60 Hz
|
Receptacle |
Hardwire
|
Output nominal voltage |
120V
|
Electric current - max |
22A
|
Runtime graph |
|
Battery type |
Valve Regulated Lead Acid (VRLA)
|
Runtime at half load |
268 min
|
Noise level |
52.4 dB maximum, front-side 1 meter
|
Relative humidity |
Up to 95% non-condensing
|
Front Panel LCD Display |
Four line text-based front panel LCD provides full access to UPS status, alarms, faults, events, settings and control options
|
Output Receptacles |
Hardwire
|
Output Receptacles Details |
Protected Line, Neutral and Ground hardwire output terminals; Includes strain relief
|
Product Features |
Individually Controllable Load Banks
Expandable Runtime |
Product Highlights |
Protects equipment against blackouts, brownouts, overvoltages, surges and line noise
Keeps power running during blackouts to allow time for safe system shutdown Recommended for remote locations where temperatures range within -40°C and 80°C Maintains continuous 120V nominal output during brownouts and overvoltages Optional WEBCARDLXMINI network interface supports Auto Probe feature Recommended for remote locations where temperatures range within -40°C and 80°C |
Nominal Output Voltage |
120V
|
Network Management Cards |
WEBCARDLXMINI
|
Network Management Cards Details |
Network management card optional
|
Output power factor |
0.8
|
Phase (input) |
Single-phase
|
Runtime at full load |
117
|
Communication interface |
DB9 Serial
USB Slot for SNMP / Web interface |
Typical Battery Runtime |
Expandable Runtime
|
Battery Charge |
Temperature compensated 2/4/6/8/10A selectable charging system; Battery temperature sensor cable included
|
Dc Voltage |
48V DC
|
Operating Temperature Range |
-40° to 176°F (-40° to 80°C)
|
Grounding Details |
Grounding lug connector provides a permanent ground connection for the UPS
|
Input Circuit Breakers |
30A breaker
|
Output Circuit Breakers |
30A breaker
|
High Voltage Transfer to Battery Power |
152V (default, adjustable from 120 to 152V)
|
Low Voltage Transfer to Battery Power |
88V (default, adjustable from 88 to 120V)
|
Undervoltage Correction |
Undervoltages from 88 to 102V are boosted by 8% (default, adjustable from 88 to 120V)
|
Application |
|
Switch configuration |
All three front-panel circuit breakers serve as power switches required to energize the UPS (DC INPUT, AC INPUT, AC OUTPUT); Three additional switches below the LCD provide SCROLL, ESCAPE and ENTER functions
|
AC suppression joule rating |
474
|
Housing material |
Steel
|
Output AC waveform (AC mode) |
Pure Sine Wave
|
Output AC waveform (battery mode) |
Pure Sine wave
|
Output Capacity (kVA) |
2
|
Output Capacity (kW) |
1.6
|
Output Capacity (VA) |
2000
|
Output Capacity Details |
Maximum output capacity is temperature dependent: 1600W (-40 to 55° C) / 1200W (55 to 75° C) and 1000W (75 to 80° C)
|
Operating Elevation |
|
Primary UPS Depth (mm) |
240
|
Primary UPS Height (mm) |
133
|
Primary UPS Width (mm) |
400
|
Audible Alarms |
Audible alarm reports Battery mode operation, Battery low status, Overload and UPS Fault conditions
|
Battery Start Capability |
Yes
|
Cooling Method |
High speed user-replaceable fan with dust filter
|
LED Indicators |
Set of 3 front panel LEDs report AC output status (green), Alarm condition (yellow) and Fault condition (red)
|
Output Voltage Regulation (Line Mode) |
120V (-14% / +8%) Factory setting, adjustable
|
Output Voltage Regulation(Battery Mode) |
120V (±4%)
|
Overvoltage Correction |
Overvoltages from 128 to 152V are reduced by 20% (default, adjustable from 120 to 144V)
|
Recommended Electrical Service |
120V AC
|
Storage Temperature |
-40° to 176°F (-40° to 80°C)
|
Included Mounting Accessory Description |
Set of two rackmount brackets support installation in 2 or 4 post racks
|
Input Connection Description |
Protected Line, Neutral and Ground hardwire input terminals; Includes strain relief
|
Input Dry Contact Ports |
1 set of input dry contacts generate an alarm of configurable input conditions when pins 1&2 are shorted; Rating: 300VDC/12A; Wiring Gauge: Up to 12AWG
|
Output Dry Contact Ports |
6 sets of output dry contacts support normally-open or normally-closed signaling of configurable UPS conditions; Rating: 300VDC/12A; Wiring Gauge: Up to 12AWG
|
LVC (Low Voltage Cut-Off) |
UPS automatically shuts off in battery mode as battery system voltage drops to 42.5V
|
Network Monitoring Port Description |
WEBCARDLXMINI network management card option supports operation from 0C to 70C as measured inside the UPS; Built-in USB and Serial ports support UPS configuration via Windows Hyperterminal session
|
Voltage Regulation Description |
Corrects brownouts and overvoltages from 88 to 152V to 120V nominal (factory default)
|
Maximum Input Amps |
22
|
Minimum Required Rack Depth (cm) |
25.4
|
Minimum Required Rack Depth (inches) |
10
|
UPS Power Module Dimensions |
5.24 x 15.750 x 9.45
|
Power Mode Transfer Time |
UPS mode: 10ms (typical) / 12ms (max); Generator mode: 20ms (typical) / 22ms (max)
|
Connected Equipment Insurance |
$250,000 Ultimate Lifetime Insurance
|
EMI AC Noise Suppression |
EMI / RFI AC Noise Suppression
|
UPS Input Connection Type |
Hardwire
|
High Availability UPS Features |
Surge/noise protection
Automatic voltage regulation (AVR) |